Cold Weather Air Source Heat Pump
Cold Weather Air Source Heat Pump
Product Details

Product details

Type: Air Source Heat Pump
Installation: Freestanding
Housing Material: stainless steel or spray coating
Use: residential, hotel, school, hospital, bath center, villa, factory
Place of Origin: China (Mainland)
Function: heating or/and hot water

Important features
1. Working air temperature range:-25℃to 45℃.
2. Copeland Enhanced vapour injection (EVI) technology scroll compressor with high COP in cold area.
3. Max water outlet temperature: 60℃.
4. Working mode is changeable between heating and hot water by 3-way valve.
5. Copeland scroll compressor.
6. R407C refrigerant.
7. Linkage function of heat pump ON/OFF controlled by external controlling system.
8. Anti-freeze function.
9. LCD display controller

Advantages
-The heat rising from the feet, which meet the human body physiological needs; large heating area and temperature uniformity; good thermal stability. The floor radiant, which can save about 20%-30% energy
With beautiful design, it also no noise and does not occup your space, low maintain cost, life for 50 years.

-Air source heat pumps (also known as ASHPs) are energy-efficient alternatives to furnaces and air conditioners. They provide efficient heating and cooling for your home all from one source. They do this by using electricity to transfer energy between indoor and outdoor air.

-In addition, they deliver one to three times more energy than the electricity they consume, which can help lower your fuel bills, especially if you are replacing older, inefficient heating and cooling systems.

-Besides, they are easy to install and require little maintenance. Multi-speed electronic controls with 24-hr. on/off timer and full-function remote control. In the winter, the system’s direction is reversed so that heat is pulled from the outside air and moved into your home.

-If you have any questions about our products, please feel free to contact us, we will be the first time to reply. Also our products are in competitive price. Fostered with a team of dexterous professionals, we have been able to offer cold weather air source heat pump for our valuable clients. 

Model

SHP08 INV

SHP11 INV

SHP16 INV

SHP17 INV

SHP23 INV

Heating   capacity                     kW

7.8

10.6

15.5

16.8

22.8

Power input                                kW

1.7

2.5

3.5

3.97

5.56

COP

4.59

4.24

4.43

4.23

4.1

Cooling capacity                       kW

8.4

10.81

15.2

15.5

23.1

Power input                                kW

2.25

2.6

3.98

3.90

5.82

EER

3.73

4.16

3.82

3.98

3.97

Power supply

230V/1Ph/50Hz

400V/3Ph/50Hz

Maximum water temperature    

60

Working outside temperature  

-20~43

Refrigerant

R410A

DC inverter compressor

Twin rotary

Evaporator

Fin-tube   heat exchanger with hydrophilic coating

Condenser

Plate heat exchanger

Dimensions (W*D*H)                mm

1115*425*710

1115*425*960

1115*425*1280

1115*425*1280

1115*425*1462

Noise Level at 1 meter          dB(A)

54

56

57

58

60

Net/gross weight                         kg

90/100

105/115

140/150

140/150

185/195

Test conditions:

Heating: outside temperature (DB/WB) =7/6, water inlet/outlet=30/35

Cooling: outside temperature (DB/WB) =35/24, water inlet/outlet=23/18

 

 

 